APC UPS Temperature Check

The APC UPS Temperature Check monitors the status and reported temperature of the environment sensor.

Basic Check information

Check Type SNMP

Instances on a Device

1

Supported MIB/System

Any APC UPS device that supports the PowerNet392 SNMP MIB.

Device Class

Other

Troubleshooting

Issue Corrective Action
Failed Please check that the correct SNMP community string is configured in Network Discovery for the device
201 Exception OID_TYPE_NOSUCHOBJECT Missing OID object on the device for specific metric

OID/Calculation

Metric Name OID/Calculation Description
Temperature 1.3.6.1.4.1.318.1.1.10.2.3.2.1.4 Displays the temperature reading reported by the temperature sensor.
Temperature Unit 1.3.6.1.4.1.318.1.1.10.2.3.2.1.5 Displays the Temperature Unit : Celsius or Fahrenheit.
Sensor Status 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 Monitors the status of the temperature sensor.
Sensor Status Description 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 Displays the current status of the temperature sensor: Connected or Disconnected.