APC UPS Temperature Check
The APC UPS Temperature Check monitors the status and reported temperature of the environment sensor.
Basic Check information
| Instances on a Device |
1 |
| Supported MIB/System |
Any APC UPS device that supports the PowerNet392 SNMP MIB. |
| Device Class |
Other |
Troubleshooting
| Failed |
Please check that the correct SNMP community string is configured in Network Discovery for the device |
| 201 Exception
OID_TYPE_NOSUCHOBJECT |
Missing OID object on the device for specific metric |
OID/Calculation
| Temperature |
1.3.6.1.4.1.318.1.1.10.2.3.2.1.4 |
Displays the temperature reading reported by the temperature sensor. |
| Temperature Unit |
1.3.6.1.4.1.318.1.1.10.2.3.2.1.5 |
Displays the Temperature Unit : Celsius or Fahrenheit. |
| Sensor Status |
1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 |
Monitors the status of the temperature sensor. |
| Sensor Status Description |
1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 |
Displays the current status of the temperature sensor: Connected or Disconnected. |