APC UPS Humidity Check

The APC UPS - Humidity Check monitors the status and reported humidity of the environment sensor.

Basic Check information

Check Type SNMP
Instances on a Device 1
Supported MIB/Systems Any APC UPS device that supports the PowerNet392 SNMP MIB, and has an attached environment sensor that reports humidity readings.
Device Class Other

Troubleshooting

Issue Corrective Action
Failed Please check that the correct SNMP community string is configured in Network Discovery for the device
201 Exception OID_TYPE_NOSUCHOBJECT Missing OID object on the device for specific metric

OID/Calculation

Metric Name

OID/Calculation

Description

Humidity 1.3.6.1.4.1.318.1.1.10.2.3.2.1.6 The humidity reading .
Sensor Status 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 Monitors the status of the humidity sensor.
Sensor Status Description 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 Displays the current status of the humidity sensor. Two values can be returned: Connected or Disconnected.