APC PDU Check
The APC PDU Check monitors the phase status of the phase (circuit) and reports the low/medium/high thresholds for that sensor, as dictated by the PDU.
Basic Check information
Check Type | SNMP |
---|---|
Instances on a Device | 3 |
Supported Systems/Applications | Any APC PDU device that supports the PowerNet392 SNMP MIB. |
Device Class | Other |
Troubleshooting
Issue | Corrective Action |
---|---|
Failed | Please check that the correct SNMP community string is configured in Network Discovery for the device |
201 Exception OID_TYPE_NOSUCHOBJECT | Missing OID object on the device for specific metric |
OID/Calculation
Metric Name |
OID/Calculation |
---|---|
Load (Amperes) | 1.3.6.1.4.318.1.1.12.2.3.1.1.2/ 10 |
Maximum Acceptable Load (Amperes) | 1.3.6.1.4.318.1.1.12.2.2.1.1.4 |
Phase Utilization | ((Load/10)/Maximum Acceptable Load)*100 |