NetBotz Temperature service
The NetBotz Temperature service monitors the status and reported temperature, in Fahrenheit and Celsius of the specified temperature sensor.
This service cannot use Self Healing.
| Service Type | SNMP |
| Instances on a Device | 68 |
| Supported Systems/Applications | Any NetBotz device that has an attached temperature sensor. |
| Device Class | Other |
| Monitored By | Windows probe |
| Scan Interval | 5 minutes |
| Temperature Sensor | To determine the name of the temperature sensors attached to the NetBotz device, query the NetBotz device with the 1.3.6.1.4.1.5528.100.4.1.1.1.1 SNMP OID. The default name is nbHawkEnc_0_TEMP. |
OID/Calculation
| Metric Name | OID/Calculation | Description |
|---|---|---|
| Temperature (\u00baC) | 1.3.6.1.4.1.5528.100.4.1.1.1.8 | The temperature reading in Celsius. |
| Temperature (\u00baF) | 1.3.6.1.4.1.5528.100.4.1.1.1.9 | The temperature reading in Fahrenheit. |
| Sensor Status | 1.3.6.1.4.1.5528.100.4.1.1.1.3 | An integer value representing whether the temperature sensor is connected or disconnected. The service transitions to a Failed state if the door switch reports a disconnected status. |
| Sensor Status Description | 1.3.6.1.4.1.5528.100.4.1.1.1.3 | A description of the sensor’s status. |