NetBotz Dew Point service
The NetBotz Dew Point service monitors the dew point reading, by default in degrees Celsius, and sensor status of the specified dew point sensor.
This service cannot use Self Healing.
Service Type | SNMP |
Instances on a Device | 68 |
Supported Systems/Applications | Any NetBotz device that has an attached dew point sensor |
Device Class | Other |
Monitored By | Windows probe |
Scan Interval | 5 minutes |
Dewpoint Sensor | To determine the name of the dew point sensors attached to the NetBotz device, query the NetBotz device with the 1.3.6.1.4.1.5528.100.4.1.3.1.1 SNMP OID. The default name is nbHawkEnc_0_DEW. |
OID/Calculation
Metric Name | OID/Calculation | Description |
---|---|---|
Dewpoint | 1.3.6.1.4.1.5528.100.4.1.3.1.8 | The dew point temperature measured in degrees Celsius. |
Dewpoint | 1.3.6.1.4.1.5528.100.4.1.3.1.9 | The dew point temperature measured in degrees Fahrenheit. |
Sensor Status | 1.3.6.1.4.1.5528.100.4.1.3.1.3 | This status is either Connected or Disconnected. The service reports a Failed Status if the sensor reports Disconnected. |
Sensor Status Description | 1.3.6.1.4.1.5528.100.4.1.3.1.3 |