NetBotz Airflow service

The NetBotz Airflow service monitors the airflow reading and airflow sensor status of the specified temperature sensor.

This service cannot use Self Healing.

Service TypeSNMP
Instances on a Device68
Supported Systems/ApplicationsAny NetBotz device that has an attached airflow sensor.
Device ClassOther
Monitored ByWindows probe
Scan Interval5 minutes
Airflow SensorTo determine the name of the airflow sensors attached to the NetBotz device, query the NetBotz device with the 1.3.6.1.4.1.5528.100.4.1.5.1.1 SNMP OID.The default name is nbHawkEnc_0_AFLW.

OID/Calculation

Metric Name OID/CalculationDescription
Airflow1.3.6.1.4.1.5528.100.4.1.5.1.8 
Sensor Status1.3.6.1.4.1.5528.100.4.1.5.1.3This status is either Connected or Disconnected. The service reports a Failed Status if the sensor reports Disconnected.
Sensor Status Description1.3.6.1.4.1.5528.100.4.1.5.1.3