APC UPS Temperature service

The APC UPS Temperature service monitors the status and reported temperature of the specified environment sensor.

Service Type

SNMP

Instances on a Device

1

Supported Systems/Applications

Any APC UPS device that supports the PowerNet392 SNMP MIB.

Device Class

Other

Monitored By

Windows probe
Scan Interval5 minutes
Environment SensorEnter the name of the monitored environment sensor. To find out the name of the environment sensor attached to the UPS, query the UPSdevice with the .1.3.6.1.4.1.318.1.1.10.2.3.2.1.2 SNMP OID. The default name is Int Sensor.

OID/Calculation

Metric NameOID/CalculationDescription
Temperature1.3.6.1.4.1.318.1.1.10.2.3.2.1.4Displays the temperature reading reported by the temperature sensor.
Temperature Unit1.3.6.1.4.1.318.1.1.10.2.3.2.1.5 Displays the Temperature Unit : Celsius or Fahrenheit.
Sensor Status1.3.6.1.4.1.318.1.1.10.2.3.2.1.3Monitors the status of the temperature sensor.
Sensor Status Description1.3.6.1.4.1.318.1.1.10.2.3.2.1.3Displays the current status of the temperature sensor: Connected or Disconnected.