APC PDU service
The APC PDU service monitors the phase status of the user-specified phase (circuit) and reports the low/medium/high thresholds for that sensor, as dictated by the PDU.
Service Type | SNMP |
Instances on a Device | 3 |
Supported Systems/Applications | Any APC PDU device that supports the PowerNet392 SNMP MIB. |
Device Class | Other |
Monitored By | Windows probe |
Scan Interval | 5 minutes |
Phase Number | Enter the phase number (1, 2, or 3) to monitor. The default is 1. The only accepted values are 1, 2, or 3. |
OID/Calculation
N-able N-central services use Reverse Polish Notation (RPN) for all calculation formulae.
Metric Name | OID/Calculation |
---|---|
Load (Amperes) | 1.3.6.1.4.1.318.1.1.12.2.3.1.1.2/ 10 |
Maximum Acceptable Load (Amperes) | 1.3.6.1.4.1.318.1.1.12.2.2.1.1.4 |
Phase Utilization | ((Load/10)/Maximum Acceptable Load)*100 |